Beluk GmbH · Schongau, Germany · System components for power factor correction and power quality
Experienced, reliable, flexible
Beluk is one of the leading manufacturers in the area of power factor control relays. Its experience in this technologically complex field dates back to 1956, and its customers have profited from its forward-looking concepts in the construction of switchgear for more than 30 years. On the basis of this know-how Beluk offers matured standard components as well as tailor-made problem solutions; the production organisation is set up in accordance with DIN EN ISO 9001:2008.
The current generation of BELUK power-factor-control relays is the result of 50 years of development: electromechanical versions to start with, electronics in the seventies, the first microcontroller relays in 1988, and today integrated interfaces for data communication. Specific relays exist for dynamic compensation, induction furnaces, medium-voltage switchgear and wind-power stations. BELUK relays “separate the chaff from the wheat” — reactive from active energy — regardless of the number of harmonics disturbing the system, and the same measuring technique is found in its power analysers. Monitoring relays for voltage, current and capacitors in medium-voltage grids as well as static switches for capacitors supplement the range.
- Power factor control relaysBLR-CX · BLR-CM-R · BLR-CM-T/RT · BLR-CM3phase
- Thyristor switchesBEL-TS 15 – 130 kvar, 400 – 690 V
- Active harmonic filterBEL-AF 35 – 120 A
- Capacitor protectionKSR1 · KSR · KSR-Z · KSR-V · VSR/VCR
- Power analyserEMM-5 with 32 meters
- Web gatewayminiSCADA — SCADA in one DIN-rail device
Energy efficiency by power factor correction
In times of shortage of resources and climate change, conservation of resources is a fundamental objective and increasing energy efficiency a core aim of policy. With the systematic use of power factor correction, energy losses in the transmission and distribution networks can be significantly reduced (with a corresponding reduction in CO₂ emissions), networks can be used more efficiently — for instance for the transmission of regenerative energy — and the reliability of planning for future energy networks can be increased.
Origin and effects of reactive power
Many electrical devices, e.g. motors, need active and reactive power. Active power is converted into mechanical power or heat losses; reactive power is needed to maintain the magnetic fields and is transferred periodically in both directions between generator and load. Vector addition of active power P and reactive power Q gives the apparent power S, which utilities must make available and transmit — generators, transformers, lines and switchgear must be sized for it. Supply companies therefore charge for reactive power above a threshold; usually a target cos φ between 1.0 and 0.9 (lagging) is specified.
Power factor correction
If the lagging power factor is corrected, for example by installing a capacitor at the load, this totally or partially eliminates the reactive power drawn from the supply. The inductive reactive power Q₁ is compensated by the capacitive reactive power Q_comp, the apparent power being reduced from S₁ to S₂. Correction is at its most effective when it is physically near to the load and uses state-of-the-art technology. In Germany, power-factor correction saves energy losses of around one nuclear power plant.
Power factor control relay BLR-CX
The intelligent regulation algorithm of Beluk switches the steps optimised and by this guarantees short compensation times combined with the smallest amount of operations; the operating cycles are shared equally to all steps. All relevant parameters are set ex works so that in nearly all cases no further adjustments are necessary to start the regulation — to start, only the correct nominal voltage is needed. A wrong connection can be corrected by starting the automatic phase correction, and for maintenance each step can be switched manually. Settings sit in two menus: “Start” (commissioning: nominal voltage, CT and VT ratio, automatic connection correction) and “Expert”.
Measuring
Voltage and current in any phase — the connection is corrected automatically. Minimum sensing current 15 mA; 5 A or 1 A CTs without any setting; wide-range SMPS for voltage measuring 90 – 550 V. With the temperature sensor the relay measures the panel temperature and switches a fan on one of the control outputs; the second threshold (or external thermostats in parallel) switches the capacitors off.
Display of information
Backlit LCD showing mains parameters (V, A, kW, kvar, kVA, kvar to target, THD U, 3rd – 19th voltage harmonic, displacement PF, PF, tan φ, Hz, temperature) and panel information (power-on hours, operating cycles per step, max. temperature, average PF, rating per step in kvar and in % of nominal). Displacement PF and the status of the outputs are shown permanently.
Monitoring
- Low-voltage switch-off against chattering of contactors
- Over-voltage switch-off for protecting the capacitors
- Overtemperature switch-off
- Monitoring of THD U and switch-off when exceeded
- Recognition of defective capacitors
- Alarm when the target cannot be reached
- Signalling of the need for maintenance
- Fan control
Order codes
| Code | Version |
|---|---|
| BLR-CX04R … CX14R | 4, 6, 8, 10, 12 or 14 relay outputs |
| BLR-CX06T / CX12T | 6 or 12 transistor outputs |
| Option -L | pluggable temperature sensor |
| Option -V | separate plug for supply voltage; measuring voltage 90 – 690 V |
| Option -MB | RS485 Modbus RTU, USB |
| Option -VT | transparent cover with lock |
| 3USB · UMS9 · 3ZWC | interface kit for retrofitting RS485/USB · data cable TTL/USB · wall-mounting bracket |
| Type of device | reactive power regulator; control variable: electrical displacement reactive power |
|---|---|
| Principle of regulation | gradational regulation — Best-Fit (starting with the biggest suitable capacitor), LIFO, Combifilter (Best-Fit with more reactive power on odd outputs), Progressive (all required outputs switched in short intervals) |
| Special features | automatic detection and correction of the phase of current and voltage connection; automatic detection of engaged outputs and adaption of capacitor ratings; over/undervoltage monitoring; THD U monitoring; overtemperature switch-off |
| Measuring and auxiliary voltage | 90 – 550 V AC, single phase, 45 – 65 Hz, 5 VA, max. fuse 6 A, VT ratio 1.0 – 350.0 |
| Current measuring | 15 mA – 6 A, single phase, burden 20 mΩ, CT ratio 1 – 9600 |
| Sign-of-life contact | relay, volt-free, N/O, max. fuse 4 A, 250 V AC / 5 A, 400 V AC / 2 A |
| Interface · ambient | TTL, rear · operation –20 … 70 °C, storage –20 … 85 °C · humidity 0 – 98 % non-condensing · overvoltage class II, pollution degree 3 |
| Standards | DIN VDE 0110-1 (IEC 60664-1:1992 + A1:2000 + A2:2002) · VDE 0411-1 (DIN EN 61010-1 / IEC 61010-1:2001) · VDE 0843-20-1:2006 (DIN EN 61326-1:2006) · VDE 0843-20-2-2:2006 |
| Control outputs | up to 14 relays, N/O, volt-free with common point, max. fuse 6 A, breaking capacity 250 V AC / 5 A, 400 V AC / 2 A |
| Terminals · casing | pluggable screw-type terminal blocks, max. 4 mm² · front plastic (UL94-V0), rear metal |
| Protection · weight · size | front IP50 (IP54 with gasket), rear IP20 · approx. 0.6 kg · 144 × 144 × 58 mm, cut-out 138 (+0.5) × 138 (+0.5) mm |
BLR-CM-R, real-time BLR-CM-T/RT and BLR-CM3phase
The BLR-CM family adds a graphical backlit LCD, THD I and the 2nd – 30th harmonics of voltage and current, energy counters (kWh import/export, kvarh inductive/capacitive), a programmable digital input for external alarms and a digital output for the fan. Measuring voltage is 50 – 530 V with a separate 230 V auxiliary supply (115 V tapping point). The optional data logger (-DM) has four parts: setup history, alarm history, a logger of measuring values in 1 – 720 min intervals (min / max / mean) and a daily logger of system information (kWh, kvarh, switching operations and step size per step, average PF and average PF of the last 24 h) — downloaded via the TTL–USB cable to a CSV file.
BLR-CM-R
6 or 12 relay outputs (BLR-CM06R / CM12R). Options: -HV for MV and HV application, -MB Modbus RTU, -DM data logger with RTC and 24 V DC digital input, -Q control characteristic Q(U) where the target PF depends on the voltage level, -VT cover.
BLR-CM-T / RT — real time
The real-time algorithm calculates the control deviation directly after measuring one mains period and switches all necessary capacitors in one operation. The hybrid version runs two algorithms: the standard one for contactor-controlled capacitors builds an optimised working point for the real-time one. Versions BLR-CM06T, CM12T (transistor, open collector 8 – 32 V DC / 100 mA) and CM12RT (6 relay + 6 transistor). Dynamic mode has no capacitor-size recognition; sizes can be detected in normal mode at the beginning.
BLR-CM3phase
Three current inputs recognise asymmetric load; the algorithm works with three-phase as well as single-phase capacitors, guaranteeing optimum compensation of unbalanced loads. Displays all values per phase L1/L2/L3 and total. Versions BLR-CM06R-3A, CM12R-3A, CM06T-3A, CM12T-3A, CM12RT-3A.
Common technical data of the BLR-CM family
| Auxiliary voltage | 230 V AC with tapping point 115 V AC ±10 %, 45 – 65 Hz, 10 VA, max. fuse 6 A |
|---|---|
| Measuring voltage | 50 – 530 V AC, single phase, 45 – 65 Hz, < 1 VA, max. fuse 6 A, VT ratio 1.0 – 350.0 |
| Current measuring | 15 mA – 6 A, single phase, burden 20 mΩ, CT ratio 1 – 9600 (×3 for BLR-CM3phase) |
| Alarm contact · digital output | relay C/O, max. fuse 4 A, 250 V AC / 5 A · relay N/O with common point, 250 V AC / 5 A, 400 V AC / 2 A (fan) |
| Digital inputs | DI1 50 – 250 V AC programmable · DI2 10 – 30 V DC for synchronising the data logger (-DM) |
| Interfaces | TTL rear · RS485 Modbus RTU slave (-MB, -DM) |
| Standards | DIN VDE 0110-1 (IEC 60664-1:1992 + A1:2000 + A2:2002) · VDE 0411-1 (DIN EN 61010-1 / IEC 61010-1:2001) · VDE 0843-20-1:2006 (DIN EN 61326-1:2006) · VDE 0843-20-2-2:2006 |
| Control outputs | up to 12 relays N/O volt-free with common point, 250 V AC / 5 A, 400 V AC / 2 A — or transistor open collector 8 – 32 V DC / 100 mA |
| Terminals · casing | pluggable screw-type terminal blocks, max. 4 mm² · front plastic (UL94-V0), rear metal |
| Protection · weight · size | front IP50 (IP54 with gasket), rear IP20 · approx. 1.0 kg · 144 × 144 × 58 mm, cut-out 138 (+0.5) × 138 (+0.5) mm |
Thyristor switches BEL-TS
BEL-TS switches capacitor steps semi-controlled on two phases (terminals L1 → C1 and L3 → C3), triggered by an 8 – 30 V DC signal drawing 2 mA at 12 V. The supply is taken directly from the power connection (a separate supply is optional on the 400 – 480 V units; 230 V 50/60 Hz on the 525 – 690 V units), consumption max. 9 VA. Recovery time is typically one period; overtemperature protection and a power LED are built in.
BEL-TS 400 – 480 V — nominal current in A at 400 / 440 / 480 V (±10 %)
| Nominal power | 400 V | 440 V | 480 V | Losses W (400/440/480) | H × W × D mm | kg | Cooling | IP |
|---|---|---|---|---|---|---|---|---|
| 15 kvar | 22 | 20 | 18 | 41 / 37 / 33 | 188 × 202 × 200 | 2.9 | AN, natural | IP20 |
| 25 kvar | 36 | 33 | 30 | 68 / 61 / 52 | 200 × 160 × 215 | 4.3 | AN, natural | IP10 |
| 50 kvar | 72 | 66 | 60 | 122 / 111 / 104 | 200 × 160 × 215 | 4.3 | AN, natural | IP10 |
| 75 kvar | 109 | 99 | 90 | 205 / 184 / 172 | 270 × 160 × 215 | 5.6 | AF, forced | IP10 |
| 100 kvar | 144 | 131 | 120 | 250 / 224 / 244 | 270 × 160 × 215 | 5.6 | AF, forced | IP10 |
| 125 kvar (480 V) | — | — | 150 | 261 | 270 × 160 × 215 | 5.6 | AF, forced | IP10 |
BEL-TS 525 – 690 V
| Nominal power | Nominal voltage | Nominal current | Losses | H × W × D mm | kg | Cooling |
|---|---|---|---|---|---|---|
| 65 kvar | 525 V | 72 A | 122 W | 200 × 160 × 215 | 4.3 | AN |
| 130 kvar | 525 V | 144 A | 250 W | 270 × 160 × 215 | 5.6 | AF |
| 50 kvar | 690 V | 42 A | 75 W | 200 × 160 × 270 | 4.6 | AN |
| 100 kvar | 690 V | 84 A | 145 W | 270 × 160 × 270 | 5.9 | AF |
| Max. altitude | 1000 m NN (higher altitudes possible with reduced current ratings) |
|---|---|
| Ambient temperature | –10 … 45 °C (up to +65 °C with reduced current ratings) |
| Humidity | 10 – 95 % without moisture condensation |
Active harmonic filter BEL-AF
Many electrical devices pollute the grid with non-linear load currents: devices disturb each other, the load on the grid is much higher than necessary and, in extreme situations, the supply can fail. Indications are harmonics, unbalanced load, neutral current and a bad power factor. BEL-AF improves voltage quality by filtering the current: it compensates harmonics up to the 51st order, balances the phase currents and improves the power factor, reducing the neutral current. Sized with sufficient reserve it also compensates the phase shift in real time. CT on the source side gives closed-loop control, on the load side open-loop control; up to 8 filters work in parallel with their current inputs connected in series.
| Compensation current | 3 phase / 3 wires — 35, 60, 90 or 120 A; current limit at full correction; inrush current less than rated current |
|---|---|
| Compensated harmonic orders | 2nd to 51st; response time < 20 ms; power factor correction ind. 0.70 – cap. 0.70 |
| Input voltage · frequency | 400 V +15 % / –20 % · 47 – 63 Hz |
| Current transformers | standard 100 A : 1 A – 10 000 A : 1 A; optional …: 5 A |
| Cooling · altitude · ambient | AF air forced · < 1000 m NN · operation 0 … +40 °C, storage –20 … +70 °C |
| Display | LCD — meter parameters, waveform and spectrum, event log up to 300 records (FIFO), all settings, up to 10 languages |
| Interfaces · I/O | RS232 / USB standard; RS485 / RS422 / Ethernet optional · 5 output dry contacts, 1 input dry contact, 1 EPO |
Unbalance protection relay KSR1
High-voltage capacitors taken into operation must be supervised all the time. Most are manufactured with insulating oil as the dielectric, which could catch fire in case of failure — with some litres of oil per capacitor there is a fire load not to be disregarded, so the capacitors must be separated from the grid before a failure causes an accident. The KSR1 protects the capacitors against internal failures in a versatile way without generating useless and expensive cut-offs: it monitors current or voltage (selectable), with two threshold levels for Alarm / Trip as absolute or % values, programmed delay times, latching or auto-reset relays, a third relay for Alarm, Trip or both, and a record of the last 5 Alarm and Trip operations. A natural unbalance can be programmed in and is subtracted from the measured value.
- Double-star connection6 identical capacitors in two stars; the CT sits in the conductor between the two star points — the current indicates the symmetry.
- H-bridge connection4 identical capacitors form an H; the CT sits in the conductor connecting the middle of the left and right branch.
- Voltage monitoring3 capacitors in star; three 2-pole insulated VTs with secondaries in series — the voltage indicates the symmetry.
| Supply voltage | 40 – 250 V AC, 45 – 65 Hz / 40 – 300 V DC, 5 VA, max. fuse 6 A |
|---|---|
| Measuring voltage | 0.2 – 20 V, burden 284 kΩ, VT ratio 1 – 350, low-pass filter; continuous overload 120 V, 500 V for 10 s; accuracy 0.5 % of upper range value |
| Current measuring | 20 mA – 5 A, burden 20 mΩ, CT ratio 1 – 4000, low-pass filter; continuous overload 25 A, 100 A for 1 s; accuracy 0.5 % |
| Relay outputs | max. 1250 VA AC, max. switching voltage 440 V AC; DC (ohmic) 30 V / 5 A, 60 V / 1 A, 110 V / 0.5 A, 220 V / 0.3 A |
| Digital input · interface | blocking Alarm / Trip via DI1 & DI2 · TTL, rear |
| Ambient · humidity | operation –20 … 70 °C, storage –40 … 85 °C · 0 – 95 % non-condensing |
| Standards | IEC 60255-1 … -5 (oscillatory waves, ESD, RF fields, fast transients, surge); DIN VDE 0110-1; VDE 0411-1; VDE 0843-20 · CE |
| Terminals · protection · weight | screw type max. 4 mm² · front IP50 (IP54 with gasket), rear IP20 · approx. 0.65 kg |
Capacitor protection relays KSR, KSR-Z and KSR-V
The KSR measurement system provides 3 voltage and 4 current channels with high-precision input filters (3 dB cut-off 2.5 – 3 kHz). N need not be connected — an internal resistor network provides an artificial N. CTs of 1 A or 5 A depending on the type, CT ratio 1 – 10 000, channel 4 (out-of-balance current) with its own ratio and one-button compensation of the natural unbalance. Nearly all displayed values are true RMS, and a full-range FFT is performed on all channels. A big backlit LCD and four context-sensitive soft-keys give instant usage without the manual.
32 protection settings
| Field | Meaning |
|---|---|
| Source | monitored value |
| Trigger | monitored value < or > the threshold |
| Limit | threshold |
| T-ON | delay after violating the threshold |
| T-OFF | delay for the alarm reset after the value becomes normal |
| Output | relays activated — 6 relay outputs (2 C/O + 4 N/O), each triggerable from several settings, programmable inverted and latching; latched relays reset only at the device |
Fault recorder (option -DM)
64 storage cells, each with SOURCE (monitored value), DATE/TIME, LIMIT and EXT-VAL (maximum measured value between violation and trip); start and end of each event stored with date and time and readable on the LCD. Option -DM also provides a Modbus interface and a digital input for blocking alarms.
Order codes — KSR-am-x by supply
| Code | Power supply |
|---|---|
| KSR-am-V / -W | 110 V DC / 220 V DC |
| KSR-am-S / -T | 24 V DC / 48 V DC |
| KSR-am-B / -C | 110 V AC / 230 V AC |
| -E | galvanically insulated current channels, 200 A for 1 s |
| -DM · -MB · -VT | Modbus + fault recorder + RTC + DI · Modbus only · transparent cover |
KSR-Z — the next generation
KSR-Z is always equipped with the fault recorder, Modbus interface and blocking input, and comes with factory-set protection settings so that only the threshold needs adjusting. Beyond the standard time delay it can use ANSI / IEC tripping curves, so alarm / trip depend on the height of the violation; calculated values such as earth fault and voltage asymmetry are available, each in two independent steps (alarm / trip), and an additional timer detects repetitive short-time violations (memory effect).
Factory-set protection settings
| Code | Monitored value | Alarm relay | Trip relay |
|---|---|---|---|
| OL | TRMS current L1, L2, L3 (greater than threshold) | 1 | 4 |
| UL | TRMS current (less than threshold) | 2 | 4 |
| OL th | thermally damped current, τ adjustable | 1 | 4 |
| OL f | fundamental current (50 / 60 Hz only) | 1 | 4 |
| UB | unbalance — current channel 4 (double star / H-bridge) | 2 | 4 |
| EF | earth fault — vector sum of the phase currents | 8 | 4 |
| VA | voltage asymmetry between all phases, in % deviation | 7 | 4 |
| OV | TRMS voltage L1-L2, L2-L3, L1-L3 (greater) | 7 | 4 |
| UV | TRMS voltage (less) | 7 | 4 |
Every setting in the alarm matrix can be shown on the display, stored in the fault recorder, blocked by the digital input, and reset automatically or manually.
Technical data KSR / KSR-Z
| Voltage measuring | ULL 95 – 550 V, ULN 55 – 318 V, 45 – 65 Hz, VT ratio 1 – 4000 |
|---|---|
| Current measuring | 50 mA – 5 A (type 5) or 20 mA – 1 A (type 1), burden 15 mΩ, external CT required, CT ratio 1 – 10 000, overload 20 % continuous, 200 A for 1 s |
| Switching outputs | 2 C/O + 4 N/O volt-free contacts, 250 V AC / 5 A; 30 V DC / 5 A ohmic; 110 V DC / 0.4 A ohmic, 0.3 A inductive |
| Fan control · interfaces | temperature sensor on rear, outputs programmable to switch a fan · TTL; RS485 Modbus RTU slave (optional on KSR, standard on KSR-Z) |
| Ambient · humidity | operation 0 … 70 °C, storage –20 … 85 °C · 0 – 95 % non-condensing; overvoltage category II, pollution degree 3 |
| Standards · connection | IEC 60255-1 … -5, DIN VDE 0110-1, VDE 0411-1, VDE 0843-20 · CE · screw type max. 2.5 mm² |
| Case · protection · size · weight | instrument case · front IP50 (IP54 with gasket), rear IP20 · 144 × 144 × 59 mm, cut-out 138 × 138 mm · ca. 650 g |
KSR-V — voltage-unbalance protection
The KSR-V provides 7 input channels: grid voltage on L1, L2, L3, (N) with a VT ratio up to 4000, and four special out-of-balance voltage channels V1 – V4 (0 – 20 V AC via VTs with open-delta secondaries, max. overload 120 V) so the unbalance of four capacitor banks can be monitored, each in two steps (Alarm / Trip) with separately adjustable threshold and delay. The FFT on the voltage channels matters because capacitors can be damaged by voltage harmonics. Order codes KSR-amv-V/W/S/T/B/C by supply (110 V DC, 220 V DC, 24 V DC, 48 V DC, 110 V AC, 230 V AC); options -MB, -VT; accessories UMS9 and 3ZWC.
| Auxiliary voltage | 230 V ±10 %, 45 – 65 Hz, 8 VA, max. fuse 6 A (110 V AC, 110 V DC and further ratings on request) |
|---|---|
| Voltage measuring | ULL 95 – 550 V, ULN 55 – 318 V, 45 – 65 Hz, VT ratio 1 – 4000 |
| Out-of-balance detection | 0 – 20 V, minimum sensitivity 0.5 V, max. 60 V continuous |
| Relay outputs | 4 N/O volt-free 250 V AC / 5 A, 110 V DC / 0.3 A inductive; optional 2 C/O |
| Display · operating | graphical LCD 128 × 64 pixel with backlight, clear-text menus · membrane keyboard with 4 soft-keys |
| Ambient | operation –20 … +70 °C, storage –30 … +80 °C; 0 – 95 % non-condensing |
| Connection · case · size | pluggable screw terminals max. 4 mm² rigid · plastic front (UL94-V0), metal rear · 144 × 144 × 59 mm · approx. 650 g |
Power analyser EMM-5
The EMM-5 offers 32 programmable thresholds on a selection of 52 measuring values, monitoring of exceeding and shortfall with alarm and drop-off delays of 0 – 600 s, and programmable alarm announcement by 2 C/O contacts (-m), 4 N/O contacts (-a), text message on the LCD, event logging with date and time (-DM), blocking of alarms in special situations such as a motor start via the digital input (-DM), and read-out over RS485 Modbus (-MB, -DM). Measuring values are recorded in programmable intervals with date, time, minimum, maximum and mean, downloaded to a CSV file through the TTL–USB converter.
Measurement values (display / monitoring / recording)
| Value | Range | Accuracy |
|---|---|---|
| ULN · ULL | 55 – 318 V · 95 – 550 V | ±0.5 % |
| I, Ith, IF — L1, L2, L3, N | 0.05 – 5 A | ±0.5 % |
| Frequency · rotation field | 45 – 65 Hz · right / left | ±0.1 Hz |
| cos φ L1, L2, L3 · λ | c 0.00 – i 0.00 · 0.00 – 1.00 | ±0.01 |
| S, P, Q — L1, L2, L3, total | 0 – 35 GVA / GW / Gvar | ±0.5 % |
| THD U · THD I | 0 – 100 % | |
| Harmonics U and I, 2nd – 63rd | 0 – 100 % | |
| Temperature | 5 – 80 °C |
Counters — 32 meters
Tariff 1: active energy import and export, reactive energy inductive and capacitive — each for L1, L2, L3 and total, 0000000.00 kWh – 4 000 000.00 GWh. Tariff 2 (option -DM) repeats the set. With -DM the meters are saved every day for a history; tariff switch-over by an external signal at the digital input or daily at a preset time.
Order codes
| Code | Contents |
|---|---|
| EMM5 | standard |
| EMM5 -m | 2 C/O contacts |
| EMM5 -am | 2 C/O + 4 N/O contacts |
| EMM5 -Im | 2 C/O contacts + 4 impulse outputs |
| -MB | RS485 Modbus RTU |
| -DM | Modbus, event recorder, measured data storage 2048 kB, real-time clock, digital input |
| -E | galvanically insulated current channels, 200 A for 1 s |
| MiniSCADA · MiniSCADA2 · UMS9 | web gateway (Ethernet, e-mail alarms, web server) · + SMS alarms and internal GPRS modem · TTL–USB converter |
| Auxiliary voltage | 230 V ±10 %, 45 – 65 Hz, 8 VA, max. fuse 6 A (110 V AC, 110 V DC on request) |
|---|---|
| Voltage measuring | ULL 95 – 550 V, ULN 55 – 318 V, 45 – 65 Hz, VT ratio 1 – 4000 |
| Current measuring | 50 mA – 6 A, 50 A for 1 s, burden < 1 VA, external CT required, CT ratio 1 – 10 000 |
| Temperature measuring | +5 … 80 °C, sensor on rear |
| Switching outputs | -a 4 N/O · -m 2 C/O — volt-free, 250 V AC / 5 A, 110 V DC / 0.3 A inductive · -I 4 pulse outputs solid state max. 250 V DC / 0.1 A |
| Interfaces · display · operating | TTL serial; optional RS485 Modbus RTU · graphical LCD 128 × 64 with backlight · membrane keyboard, 4 soft-keys |
| Ambient · humidity | operation –20 … +70 °C, storage –30 … +80 °C · 0 – 95 % non-condensing; overvoltage category II, pollution degree 3 |
| Connection · case · protection · size | pluggable screw terminals max. 4 mm² · plastic front (UL94-V0), metal rear · front IP50 (IP54 with gasket), rear IP20 · 144 × 144 × 59 mm, cut-out 138 × 138 mm, approx. 650 g |
Voltage control relay VSR / VCR
The VSR (three-phase) and VCR (single-phase) monitor grids and detect dangerous situations for connected capacitors or other electronic devices. Capacitors in compensation panels can be damaged by overloading or voltage peaks, so monitoring the voltage including harmonics is recommended: on violation of a threshold the display shows it and a relay can switch the capacitors off. True-RMS values and a full-range FFT on the 3 / 1 voltage channels; big backlit LCD with four soft-keys.
| Voltage measuring | 55/95 – 318/550 V, 45 – 65 Hz, ratio 1 – 4000 |
|---|---|
| Switching outputs | 2 C/O + 4 N/O volt-free contacts, max. fuse gL 6 A; breaking capacity 250 V AC / 5 A, 30 V DC / 5 A ohmic, 110 V DC / 0.4 A ohmic, 0.3 A inductive |
| Fan control · interfaces | rear temperature sensor, outputs programmable for a fan · TTL; optional RS485 Modbus RTU slave |
| Order codes | VCR-am-V/W/S/T/B/C (single phase) · VSR-am-V/W/S/T/B/C (three phase) — supply 110 V DC, 220 V DC, 24 V DC, 48 V DC, 110 V AC, 230 V AC; options -MB, -VT (IP54); accessories UMS9, 3ZWC |
| Ambient · standards · size | operation 0 … +70 °C, storage –20 … +85 °C · DIN VDE 0110-1, VDE 0411-1, VDE 0843-20, CE · 144 × 144 × 59 mm, ca. 650 g |
Configurable web gateway miniSCADA
The miniSCADA is an easy-to-use web-based SCADA system for local and remote monitoring and control over Ethernet, internet, LANs, telephone modems, GSM (external modem) and GPRS. Its built-in web server is used to customise the graphical interface: connect the Modbus devices, select the desired data — up to 400 Modbus registers — and it appears on the onboard web pages without HTML programming, Windows tools, licences or royalties. Up to 64 alarms are sent by e-mail or SMS with user-defined text and stored in an alarm history; up to 64 parameters are logged at 10 s – 60 min sample rates with trend graphs and CSV download. As a Modbus TCP gateway it acts as a transparent bridge between serial Modbus RTU devices and SCADA systems or PLCs. Security: user name and password assigned by the administrator; the database is kept consistent on power loss.
- Simple installationcomplete SCADA system in one DIN-rail device, no software on the PC
- Web server with up to 30 pagesdisplay and parametrising in any browser, also via internet
- 64 programmable alarmsby e-mail, or SMS with MiniSCADA2 (internal GPRS modem)
- Modbus master for up to 32 devicesBLR-CM, BLR-CM3phase, KSR and any RS485 Modbus RTU slave
| Ethernet protocols · baud rate | Modbus TCP, HTTP, SMTP, FTP, SNMP · 10 / 100 Mbit/s |
|---|---|
| Serial interfaces | #1 RS232 / RS485 for Modbus RTU / ASCII · #2 RS232 with full modem support · network baud rate up to 57.6 kbit/s |
| Power supply · consumption | 9 – 32 V AC/DC · 50 mA at 24 V |
| Operating temperature · humidity | 0 … +60 °C · 5 – 93 % RH non-condensing |
| Certifications | EN 50081-2:1993 and EN 61000-6-2:1999 |
| Housing | grey plastic, Lexan 940, self-extinguishing UL94-V0; DIN-rail mounting, 4 modules, IP20; 90 × 70 × 58 mm |